Operation
2
The OUTPUT FREQUENCY selection screen will appear.
OUTPUTFREQUENCYreferstothecycles-per-second(Hz)ofUPSoutputpower.Thisvalueis
mostcommonlysettomatchtheprevailingcountryorregion-specificfrequency.Ingeneral,in
theUSA,CanadaandMexicousethe60Hzfactorysetting.In100-127V50Hzlocations,such
asJamaica,AntiguaandpartsofJapan,settheUPSto50Hz.Tosuccessfullyconfigureyour
UPStoconvertfrequencyfrom50-to-60Hzor60-to-50Hz,setBOTHtheOUTPUTFREQUENCY
tothedesiredsettingandenablethisfunctionbysettingtheFREQCONVERSIONtoENABLE.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
60Hz(factory),50Hz
To leave UPS setup mode,
PRESS andHOLD theSETUP
BUTTON (about 3 seconds).
NOTE-theUPSmustbeinSTANDBYMODE
tochangetheoutputfrequencysetting
3
The FREQUENCY CONVERTER selection screen will appear.
FREQUENCYCONVERTERreferstotheabilityoftheUPStoconvert60Hzto50Hzor50Hzto
60Hz.TheUPSsystemautomaticallyselects50Hzor60Hzoperationbasedonutilitypower
conditions at start-up. The factory configuration of OFF is ideal for most applications. Some
usersmaywishtoconvertfrequencyforconnectedequipment.Tosuccessfullyconfigureyour
UPSforfrequencyconversion,turnONtheFREQUENCYCONVERTERfunctionandSETthe
OUTPUTFREQUENCYfunctiontothedesired50or60Hzsetting.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen , press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
OFF(factory), ON
To leave UPS setup mode,
PRESS andHOLD theSETUP
BUTTON (about 3 seconds).
NOTE-theUPSmustbeinSTANDBYMODE
tochangethefrequencyconvertersetting
4
The BYPASS RANGE selection screen will appear.
BYPASS RANGE: Sets the allowable voltage deviation from nominal input voltage that is
acceptable for the unit to go to bypass in a fault condition. If the voltage goes outside the range,
the unit will not go to bypass. If the unit is already in bypass, it will turn the output off. The factory
settingofWIDEiscompatiblewiththevastmajorityofnetworkingequipment.Regardlessofthe
“plusorminus”valueentered,thehighestbypassvoltageavailableis135V.Thelowestbypass
voltageavailableis90V(fullload)and70V(<70%load).The“Wide”rangereflectsthesesame
values(fullload90to135V/<70%load70to135V).
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
HI(factory),5%,6%,7%,8%,
9%, 10%, 11%, 12%, 13%,
14%, 15%
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
13-03-138 93-3168-EN.indd 22 3/28/2013 1:05:38 PM