23
Operation
5
The ECONOMY MODE selection screen will appear.
ECONOMYMODEisaUPSsettingthatenablesenhancedefficiencyandreducedBTUoutput
by suspending double-conversion circuits whenever input power is already of sufficient
qualitytorunconnectedequipment.Ifenabled,theUPSwillrunineconomymodewhenthe
voltage is within ±10% of nominal. If the voltage goes beyond the ±10% range, the UPS
returns to on-line mode.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
OFF (factory), ON
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
NOTE-theUPSmustbeinSTANDBYMODE
to change the economy mode setting
6
The AUDIBLE ALARM selection screen will appear.
The AUDIBLE ALARM screen gives the user the ability to permanently enable or disable the
UPS’s audible alarm in case of an alarm event. The factory configuration of ON is ideal for
mostapplications.Certainapplicationsmayrequirethealarmtobedisabled,inwhichcase
the option of OFF can be selected.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
ON (factory), OFF
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
7
The OVERLOAD ALARM selection screen will appear.
OVERLOADALARMreferstothepointatwhichtheUPSwillsoundits’overloadalarm.Thefactory
settingof105%willprovideadequateoverloadwarningsformostapplications,butalternative
values from 5% to the 105% default (in 5% intervals) are available for custom configurations.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
105% (factory), 95%, 85%,
75%,65%,55%,45%,35%,
25%, 15%, 5%
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).