A SERVICE OF

logo

23
Operation
5
The ECONOMY MODE selection screen will appear.
ECONOMYMODEisaUPSsettingthatenablesenhancedefficiencyandreducedBTUoutput
by suspending double-conversion circuits whenever input power is already of sufficient
qualitytorunconnectedequipment.Ifenabled,theUPSwillrunineconomymodewhenthe
voltage is within ±10% of nominal. If the voltage goes beyond the ±10% range, the UPS
returns to on-line mode.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
OFF (factory), ON
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
NOTE-theUPSmustbeinSTANDBYMODE
to change the economy mode setting
6
The AUDIBLE ALARM selection screen will appear.
The AUDIBLE ALARM screen gives the user the ability to permanently enable or disable the
UPS’s audible alarm in case of an alarm event. The factory configuration of ON is ideal for
mostapplications.Certainapplicationsmayrequirethealarmtobedisabled,inwhichcase
the option of OFF can be selected.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
ON (factory), OFF
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
7
The OVERLOAD ALARM selection screen will appear.
OVERLOADALARMreferstothepointatwhichtheUPSwillsoundits’overloadalarm.Thefactory
settingof105%willprovideadequateoverloadwarningsformostapplications,butalternative
values from 5% to the 105% default (in 5% intervals) are available for custom configurations.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
105% (factory), 95%, 85%,
75%,65%,55%,45%,35%,
25%, 15%, 5%
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
13-03-138 93-3168-EN.indd 23 3/28/2013 1:05:42 PM