5.2 Troubleshooting Flow Charts (continued)
5.2.13 “TRANSFORMER OVERHEAT”
5 Troubleshooting (continued)
Fig 5.2.13a
Fig 5.2.13b
Note (1): Models with C–cabinets are: SU40K, SU60K, SU80K, SU60KTV and SU80KTV.
Note (2): See Figure 5.2.13b for location.
Note (3): For the location of the NH-SYS-M board, turn to section 1.5. To replace the NHS-SYS-M board, remove the EEPROM chip from the old
NHS-SYS-M board and insert it into the new one.
Start
Is the UPS loading
too high?
Reduce loading
N
Y
END
Is it a
C-Cabinet model ?
(1)
Replace M board
(3)
N
N
YY
in CNM10 and
CNM11?
Are short-pins
(2)
Are the
W38 plug in CNM11
and W39 plug in
CNM10?
(2)
Plug in short-pins
Plug in these wires