5.2 Troubleshooting Flow Charts (continued)
5.2.16 “PARALLEL FAILURE”
5 Troubleshooting (continued)
Start
Are both
system’s EEPROM
power rating settings
the same?
(1)
Make sure that parallel
(2)
IDs are different
N
Y
END
Make sure the units
are identical.
Synchronize power
rating settings
(1)
Fig 5.2.16a
Fig 5.2.16b
Note (1): Figure 5.2.16b shows the EEPROM’s power rating settings (Rating VA). To learn about EEPROM parameter settings, turn to section 3.2.
Note (2): Access parallel ID settings using the LCD control panel (bypass mode only). (UPS SETUP
LOCAL SETUP PARALLEL ID)