A SERVICE OF

logo

35
PERFORMANCE AND ELECTRICAL DATA
MODEL 52PQ (265-1-60)
LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 380-93.
†Coefficient of Performance (COP) at 47 F outdoor ambient
temperature.
**Electric resistance heater power and fan motor power.
††All 265-v units require an electrical subbase (receptacle or hard-
wire model).
RECEPTACLES AND FUSE TYPES
LEGEND
MODEL
NUMBER
52PQ
CAPACITY* (Btuh)
HEATER
kW
EER COP†
VOLTAGE
RANGE
AMPS WATTS
Cooling
Heating
Cooling Heating** Cooling Heating
Rev. Cycle Electric
207---4 7,200 6,300 7,800 2.3 12.3 3.4
239-292
2.4 9.2 585 2396
307---4 7,200 6,300 11,600 3.4 12.3 3.4 2.4 13.3 585 3496
209---4 9,100 7,700 7,800 2.3 11.5 3.2 3.1 9.2 791 2396
309---4 9,100 7,700 11,600 3.4 11.5 3.2 3.1 13.3 791 3496
212---4 12,100 10,800 7,800 2.3 11.1 3.2 4.2 9.4 1090 2470
312---4 12,100 10,800 11,600 3.4 11.1 3.2 4.2 13.5 1090 3570
512---4 12,100 10,800 17,000 5.0 11.1 3.2 4.2 19.6 1090 5170
215---4 14,700 14,100 7,800 2.3 9.7 3.0 5.7 9.4 1515 2470
315---4 14,700 14,100 11,600 3.4 9.7 3.0 5.7 13.5 1515 3570
515---4 14,700 14,100 17,000 5.0 9.7 3.0 5.7 19.6 1515 5170
MODEL
NUMBER
52PQ
POWER
FACTOR
%
FAN MOTOR
MAX. FUSE
SIZE
(Amps)
MIN.
CIRCUIT
AMPS
RECEP-
TACLE
TYPE††
R-22
CHARGE
(oz)
DEHUMIDI-
FICATION
(Pints/Hr)
SENSIBLE
HEAT
FACTOR
APPROX.
CHASSIS
SHIP WT
(lb)
Horsepower
Full
Load
Amps
Indoor
CFM
LO/HI
207---4
97 0.075 0.46 220/260
15 11.3 A
26 1.5 0.78 125
307---4 20 16.5 B
209---4
97 0.075 0.46 220/260
15 11.3 A
24 2.4 0.73 125
309---4 20 16.5 B
212---4
99 0.125 0.71 270/340
15 11.6 A
34 3.4 0.71 140312---4 20 16.7 B
512---4 25 24.3 C
215---4
96 0.125 0.71 250/320
15 11.6 A
33 4.6 0.67 150315---4 20 16.7 B
515---4 25 24.3 C
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E
UNIT NAMEPLATE VOLTAGE 265
OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
OUTLET BLADE CONFIGURATION
ABC
NEMA CONFIGURATION 7-15R 7-20R 7-30R
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
15 20 30
HEATER (KILOWATTS) 2.3 3.4 5.0
HACR Heating, Air Conditioning, and Refrigeration
NEMA National Electrical Manufacturers Association