39
PERFORMANCE AND ELECTRICAL DATA
MODEL 52CQ (265-1-60)
LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 380-93.
†Coefficient of Performance (COP) at 47 F outdoor ambient
temperature.
**Electric resistance heater power and fan motor power.
††All 265-v units require an electrical subbase (receptacle or hard-
wire model).
RECEPTACLES AND FUSE TYPES
LEGEND
MODEL
NUMBER
52CQ
CAPACITY* (Btuh)
HEATER
kW
EER COP†
VOLTAGE
RANGE
AMPS WATTS
Cooling
Heating
Cooling Heating** Cooling Heating
Rev. Cycle Electric
207---4 7,000 6,100 7,800 2.3 11.1 3.1
239-292
2.6 9.2 631 2396
307---4 7,000 6,100 11,600 3.4 11.1 3.1 2.6 13.3 631 3496
209---4 8,900 7,700 7,800 2.3 10.7 3.1 3.6 9.2 832 2396
309---4 8,900 7,700 11,600 3.4 10.7 3.1 3.6 13.3 832 3496
212---4 12,000 10,800 7,800 2.3 10.1 3.0 4.7 9.4 1188 2470
312---4 12,000 10,800 11,600 3.4 10.1 3.0 4.7 13.5 1188 3570
512---4 12,000 10,800 17,000 5.0 10.1 3.0 4.7 19.6 1188 5170
215---4 14,600 14,100 7,800 2.3 9.5 3.0 5.7 9.4 1537 2470
315---4 14,600 14,100 11,600 3.4 9.5 3.0 5.7 13.5 1537 3570
515---4 14,600 14,100 17,000 5.0 9.5 3.0 5.7 19.6 1537 5170
MODEL
NUMBER
52CQ
POWER
FACTOR
%
FAN MOTOR
MAX. FUSE
SIZE
(Amps)
MIN.
CIRCUIT
AMPS
RECEP-
TACLE
TYPE††
R-22
CHARGE
(oz)
DEHUMIDI-
FICATION
(Pints/Hr)
SENSIBLE
HEAT
FACTOR
APPROX.
CHASSIS
SHIP WT.
(lb)
Horsepower
Full
Load
Amps
Indoor
CFM
LO/HI
207---4
97 0.075 0.46 220/260
15 11.3 A
26 1.5 0.78 125
307---4 20 16.5 B
209---4
97 0.075 0.46 220/260
15 11.3 A
28 2.4 0.73 125
309---4 20 16.5 B
212---4
99 0.125 0.71 270/340
15 11.6 A
29 3.4 0.71 140312---4 20 16.7 B
512---4 25 24.3 C
215---4
96 0.125 0.71 250/320
15 11.6 A
33 4.6 0.67 150315---4 20 16.7 B
515---4 25 24.3 C
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E
UNIT NAMEPLATE VOLTAGE 265
OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
OUTLET BLADE CONFIGURATION
ABC
NEMA CONFIGURATION 7-15R 7-20R 7-30R
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
15 20 30
HEATER (KILOWATTS) 2.3 3.4 5.0
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association