133
APPENDIX A — LOCAL DISPLAY TABLES
MODE — RUN STATUS
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
VIEW AUTO VIEW OF RUN STATUS
→HVAC ascii string spelling out the hvac modes string 90,92
→OCC Occupied ? YES/NO OCCUPIED forcible 90,92
→MAT Mixed Air Temperature dF MAT 90,92
→EDT Evaporator Discharge Tmp dF EDT 90,92
→LAT Leaving Air Temperature dF LAT 90,92
→EC.C.P Economizer Control Point dF ECONCPNT 90,92
→ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 90,92
→EC2.P Economzr Act.Curr.Pos. 0-100 % ECON2POS 90,92
→CL.C.P Cooling Control Point dF COOLCPNT 90,92
→C.CAP Current Running Capacity CAPTOTAL 90,92
→CL.ST Requested Cool Stage CL_STAGE 90,92
→HT.C.P Heating Control Point dF HEATCPNT 90,92
→HT.ST Requested Heat Stage HT_STAGE 90,92
→H.MAX Maximum Heat Stages HTMAXSTG 90,92
ECON ECONOMIZER RUN STATUS
→ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 69,93
→EC2.P Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS 69,93
→ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible 69,93
→ACTV Economizer Active ? YES/NO ECACTIVE 69,93
→DISA
ECON DISABLING CONDITIONS
→DISA→UNV.1 Econ Act. Unavailable? YES/NO ECONUNAV 69,93
→DISA→UNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV 69,93
→DISA→ENTH Enth. Switch Read High ? YES/NO ENTH 69,93
→DISA→DBC DBC - OAT Lockout? YES/NO DBC_STAT 69,93
→DISA→DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT 69,93
→DISA→DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT 69,93
→DISA→OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT 69,93
→DISA→DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT 69,93
→DISA→EDT EDT Sensor Bad? YES/NO EDT_STAT 69,93
→DISA→OAT OAT Sensor Bad ? YES/NO OAT_STAT 69,93
→DISA→FORC Economizer Forced ? YES/NO ECONFORC 69,93
→DISA→SFON Supply Fan Not On 30s ? YES/NO SFONSTAT 69,93
→DISA→CLOF Cool Mode Not In Effect? YES/NO COOL_OFF 69,93
→DISA→OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD 69,93
→DISA→HELD Econ Recovery Hold Off? YES/NO ECONHELD 69,93
→DISA→DH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL 69,93
→O.AIR OUTSIDE AIR INFORMATION 69,93
→O.AIR→OAT Outside Air Temperature dF OAT forcible 69,93
→O.AIR→OA.RH Outside Air Rel. Humidity % OARH forcible 69,93
→O.AIR→OA.E Outside Air Enthalpy OAE 69,93
→O.AIR→OA.D.T OutsideAir Dewpoint Temp dF OADEWTMP 69,93
COOL COOLING INFORMATION
→C.CAP Current Running Capacity % CAPTOTAL 92,93
→CUR.S Current Cool Stage COOL_STG 92,93
→REQ.S Requested Cool Stage CL_STAGE 92,93
→MAX.S Maximum Cool Stages CLMAXSTG 92,93
→DEM.L Active Demand Limit % DEM_LIM forcible 92,93
→SUMZ
COOL CAP. STAGE CONTROL
→SUMZ→SMZ Capacity Load Factor -100 → +100 SMZ 92,93
→SUMZ→ADD.R Next Stage EDT Decrease ^F ADDRISE 92,93
→SUMZ→SUB.R Next Stage EDT Increase ^F SUBRISE 92,93
→SUMZ→R.PCT Rise Per Percent Capacity RISE_PCT 92,93
→SUMZ→Y.MIN Cap Deadband Subtracting Y_MINUS 92,93
→SUMZ→Y.PL U Cap Deadband Adding Y_PLUS 92,93
→SUMZ→Z.MIN Cap Threshold Subtracting Z_MINUS 92,93
→SUMZ→Z.PLU Cap Threshold Adding Z_PLUS 92,93
→SUMZ→H.TMP High Temp Cap Override HI_TEMP 92,93
→SUMZ→L.TMP Low Temp Cap Override LOW_TEMP 92,93
→SUMZ→PULL Pull Down Cap Override PULLDOWN 92,93
→SUMZ→SLOW Slow Change Cap Override SLO_CHNG 92,93
TRIP MODE TRIP HELPER
→UN.C.S Unoccup. Cool Mode Start UCCLSTRT 93
→UN.C.E Unoccup. Cool Mode End UCCL_END 93
→OC.C.S Occupied Cool Mode Start OCCLSTRT 93
→OC.C.E Occupied Cool Mode End OCCL_END 93
→TEMP Ctl.Temp RAT,SPT or Zone CTRLTEMP 93
→OC.H.E Occupied Heat Mode End OCHT_END 93
→OC.H.S Occupied Heat Mode Start OCHTSTRT 93
→UN.H.E Unoccup. Heat Mode End UCHT_END 93
→UN.H.S Unoccup. Heat Mode Start UCHTSTRT 93
→HVAC ascii string spelling out the hvac modes string 93
LINK CCN - LINKAGE
→MODE Linkage Active - CCN ON/OFF MODELINK 94
→L.Z.T Linkage Zone Control Tmp dF LZT 94
→L.C.SP Linkage Curr. Cool Setpt dF LCSP 94
→L.H.SP Linkage Curr. Heat Setpt dF LHSP 94
HRS COMPRESSOR RUN HOURS
→HR.A1 Compressor A1 Run Hours 0-999999 HRS HOURS_A1 config 94
→HR.A2 Compressor A2 Run Hours 0-999999 HRS HOURS_A2 config 94
→HR.B1 Compressor B1 Run Hours 0-999999 HRS HOURS_B1 config 94
→HR.B2 Compressor B2 Run Hours 0-999999 HRS HOURS_B2 config 94
STRT COMPRESSOR STARTS
→ST.A1 Compressor A1 Starts 0-999999 CY_A1 config 94
→ST.A2 Compressor A2 Starts 0-999999 CY_A2 config 94
→ST.B1 Compressor B1 Starts 0-999999 CY_B1 config 94
→ST.B2 Compressor B2 Starts 0-999999 CY_B2 config 94
VERS SOFTWARE VERSION NUMBERS
→MBB CESR131292-xx-xx string 94
→RCB CESR131249-xx-xx string 94
→ECB CESR131249-xx-xx string 94
→SCB CESR131226-xx-xx string 94
→CEM CESR131174-xx-xx string 94
→ECON xx-xx-xxx-xxx-xx string 94
→IGV xx-xx-xxx-xxx-xx string 94
→HUMD xx-xx-xxx-xxx-xx string 94
→HEAT xx-xx-xxx-xxx-xx string 94
→BP1 xx-xx-xxx-xxx-xx string 94
→BP2 xx-xx-xxx-xxx-xx string 94
→MARQ CESR131171-xx-xx string 94
→NAVI CESR130227-xx-xx string 94