CL-4
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
BP (cont)
→FAN.T FAN TRACKING CONFIG
→FAN.T→FT.CF Fan Track Learn Enable Yes/No No
→FAN.T→FT.TM Fan Track Learn Rate 5-60 min 15
→FAN.T→FT.ST Fan Track Initial DCFM -20000 - 20000 CFM 2000
→FAN.T→FT.MX Fan Track Max Clamp 0 - 20000 CFM 4000
→FAN.T→FT.AD Fan Track Max Correction 0 -20000 CFM 1000
→FAN.T→FT.OF Fan Track Internl EEPROM -20000 - 20000 CFM 0
→FAN.T→FT.RM Fan Track Internal RAM -20000 - 20000 CFM 0
→FAN.T→FT.RS Fan Track Reset Internal Yes/No No
→FAN.T→SCF.C Supply Air CFM Config 1 - 2 (multi-text strings) 1
→B.PID BLDG.PRESS.PID CONFIGS
→B.PID→BP.TM Bldg.Pres.PID Run Rate 5 - 120 sec 10
→B.PID→BP.P Bldg.Press. Prop. Gain 0 - 5 0.5
→B.PID→BP.I Bldg.Press. Integ. Gain 0 - 2 0.5
→B.PID→BP.D Bldg.Press. Deriv. Gain 0 - 5 0.3
→ACT.C BLDG.PRES. ACTUATOR CFGS
→ACT.C→BP.1 BLDG.PRES. ACT.1 CONFIGS
→ACT.C→BP.1→SN.1 BP 1 Serial Number 1 0 - 255 0
→ACT.C→BP.1→SN.2 BP 1 Serial Number 2 0 - 255 0
→ACT.C→BP.1→SN.3
BP 1 Serial Number 3 0 - 255 0
→ACT.C→BP.1→SN.4 BP 1 Serial Number 4 0 - 255 0
→ACT.C→BP.1→SN.5 BP 1 Serial Number 5 0 - 255 0
→ACT.C→BP.1→C.A.LM BP1 Cntrl Angle Lo Limit 0-90 35
→ACT.C→BP.2 BLDG.PRES. ACT.2 CONFIGS
→ACT.C→BP.2→SN.1 BP 2 Serial Number 1 0 - 255 0
→ACT.C→BP.2→SN.2 BP 2 Serial Number 2 0 - 255 0
→ACT.C→BP.2→SN.3 BP 2 Serial Number 3 0 - 255 0
→ACT.C→BP.2→SN.4 BP 2 Serial Number 4 0 - 255 0
→ACT.C→BP.2→SN.5 BP 2 Serial Number 5 0 - 255 0
→ACT.C→BP.2→C.A.LM BP2 Cntrl Angle Lo Limit 0-90 35
D.LV.T COOL/HEAT SETPT. OFFSETS
→L.H.ON Dmd Level Lo Heat On -1 - 2 ^F 1.5
→H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F 0.5
→L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2.0 ^F 1.0
→L.C.ON Dmd Level Lo Cool On -1 - 2 ^F 1.5
→H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F 0.5
→L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2.0 ^F 1.0
→C.T.LV Cool Trend Demand Level 0.1 - 5.0 ^F 0.1
→H.T.LV Heat Trend Demand Level 0.1 - 5.0 ^F 0.1
→C.T.TM Cool Trend Time 30 - 600 sec 120
→H.T.TM Heat Trend Time 30 - 600 sec 120
DMD.L DEMAND LIMIT CONFIG.
→DM.L.S Demand Limit Select 0 - 3 (multi-text strings) 0
→D.L.20 Demand Limit at 20 ma 0 - 100% 100
→SH.NM Loadshed Group Number 0 - 99 0
→SH.DL Loadshed Demand Delta 0 - 60% 0
→SH.TM Maximum Loadshed Time 0 - 120 min 60
→D.L.S1 Demand Limit Sw.1 Setpt. 0 - 100% 80
→D.L.S2 Demand Limit Sw.2 Setpt. 0 - 100% 50
IAQ INDOOR AIR QUALITY CFG.
→DCV.C DCV ECONOMIZER SETPOINTS
→DCV.C→EC.MN Economizer Min.Position 0 - 100% 5
→DCV.C→IAQ.M IAQ Demand Vent Min.Pos. 0 - 100% 0
→DCV.C→O.C.MX Economizer Min.Flow 0 - 20000 CFM 2000
→DCV.C→O.C.MN IAQ Demand Vent Min.Flow 0 - 20000 CFM 0
→DCV.C→O.C.DB Econ.Min.Flow Deadband 200 - 1000 CFM 400
→AQ.CF AIR QUALITY CONFIGS
→AQ.CF→IQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) 0
→AQ.CF→IQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) 0
→AQ.CF→IQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) 0
→AQ.CF→IQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) 0
→AQ.CF→OQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) 0