141
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — TIMECLOCK
MODE — OPERATING MODES
MODE — ALARMS
ACRONYM NAME RANGE UNITS CNN POINT DEFAULTS PAGE NO.
TIME TIME OF DAY
→HH.MM Hour and Minute 00:00 TIME 84,85
DATE MONTH,DATE,DAY AND YEAR
→MNTH Month of Year multi-text strings MOY 84,85
→DOM Day of Month 0-31 DOM 84,85
→DAY Day of Week multi-text strings DOWDISP 84,85
→YEAR Year e.g. 2003 YOCDISP 84,85
SCH.L LOCAL TIME SCHEDULE
→PER.1 PERIOD 1 84,85
→PER.1→DAYS DAY FLAGS FOR PERIOD 1 Period 1 only 84,85
→PER.1→DAYS→MON Monday in Period YES/NO PER1MON Yes 84,85
→PER.1→DAYS→TUE Tuesday in Period YES/NO PER1TUE Yes 84,85
→PER.1→DAYS→WED Wednesday in Period YES/NO PER1WED Yes 84,85
→PER.1→DAYS→THU Thursday in Period YES/NO PER1THU Yes 84,85
→PER.1→DAYS→FRI Friday in Period YES/NO PER1FRI Yes 84,85
→PER.1→DAYS→SAT Saturday in Period YES/NO PER1SAT Yes 84,85
→PER.1→DAYS→SUN Sunday in Period YES/NO PER1SUN Yes 84,85
→PER.1→DAYS→HOL Holiday in Period YES/NO PER1HOL Yes 84,85
→PER.1→OCC Occupied from 00:00 PER1_OCC 00:00 84,85
→PER.1→UNC Occupied to 00:00 PER1_UNC 24:00 84,85
Repeated for periods 2 to 8
HOL.L LOCAL HOLIDAY SCHEDULES
→HD.01 HOLIDAY SCHEDULE 01 84,85
→HD.01→MON Holiday Start Month 0-12 HOL_MON1 84,85
→HD.01→DAY Start Day 0-31 HOL_DAY1 84,85
→HD.01→LEN Duration (Days) 0-99 HOL_LEN1 84,85
Repeated for holidays 2 to 30 84,85
DAY.S DAYLIGHT SAVINGS TIME
DS.ST DAYLIGHT SAVINGS START 84,85
DS.ST
→ST.MN Month 1 - 12 STARTM 4 84,85
DS.ST
→ST.WK Week 1 - 5 STARTW 1 84,85
DS.ST
→ST.DY Day 1 - 7 STARTD 7 84,85
DS.ST→MIN.A Minutes to Add 0 - 90 MINADD 60 84,85
DS.SP DAYLIGHTS SAVINGS STOP
DS.SP
→SP.MN Month 1 - 12 STOPM 10 84,85
DS.SP→SP.WK Week 1 - 5 STOPW 5 85
DS.SP
→SP.DY Day 1 - 7 STOPD 7 85
DS.SP
→MIN.S Minutes to Subtract 0 - 90 MINSUB 60 85
ITEM EXPANSION RANGE UNITS CCN POINT
SYS.M ascii string spelling out the system mode string
HVAC ascii string spelling out the hvac modes string
CTRL ascii string spelling out the "control type" string
MODE MODES CONTROLLING UNIT
→OCC Currently Occupied ON/OFF MODEOCCP
→T.OVR Timed Override in Effect ON/OFF MODETOVR
→DCV DCV Resetting Min Pos ON/OFF MODEADCV
→SA.R Supply Air Reset ON/OFF MODESARS
→DMD.L Demand Limit in Effect ON/OFF MODEDMLT
→T.C.ST Temp.Compensated Start ON/OFF MODETCST
→IAQ.P IAQ Pre-Occ Purge Active ON/OFF MODEIQPG
→LINK Linkage Active - CCN ON/OFF MODELINK
→LOCK Mech.Cooling Locked Out ON/OFF MODELOCK
→H.NUM HVAC Mode Numerical Form number MODEHVAC
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
CURR CURRENTLY ACTIVE ALARMS
this is a dynamic list of active alarms strings
R.CUR Reset All Current Alarms YES/NO ALRESET ram config
HIST ALARM HISTORY
this is a record of the last 20 alarms strings