If M1= 4 then S1-D1>LA;
If M2= 1 then S2-H2>LA;
If M2= 2 then S2+H2
<HA;
If M2= 3 then S2+D2
<HA;
If M2= 4 then S2-D2>LA;
If M1= 1 and M2 = 2
then S1-H1>S2+H2, S2>LA, HA>S1;
If M1 = 2 and M2 = 1
then S2-H2>S1+H1, S1>LA, HA>S2;
If M1 = 3 and M2 = 2
then S1>S2+H2, S2>LA, HA>S1+D1;
If M1 = 2 and M2 = 3
then S1+H1<S2, S1>LA, HA>S2+D2;
If M1 = 4 and M2 = 1
then S1<S2–H2, S1–D1>LA, HA>S2;
If M1 = 1 and M2 = 4
then S1–H1>S2, S2–D2>LA, HA>S1;
If M1 = 3 and M2 = 4
then S1>S2, S2–D2>LA, HA>S1+D1;
If M1 = 4 and M2 = 3
then S2>S1, S1–D1>LA, HA>S2+D2;
where the minimum deviation (D1 or D2) is 0.5% of the maxi-
mum range value.
Note When a wrong setup value is confirmed,
the controller does not skip to the next setup
item but remains in the current item dis-
playing a flashing “ERROR” indicator un-
til the parameter value is changed by the
user (the same is also true for the setup code selection).
Note In some circumstances, the user cannot succeed in setting a
parameter to a desired value if the related parameters are not
changed beforehand; e.g. to set a EC high setpoint to 10.0
mS the high alarm must be set to a value greater than 10.0
mS first.