A SERVICE OF

logo

Specifications - Environmental and Operating Conditions
170 HC900 Hybrid Controller Installation and User Guide Revision 5
9/03
Environmental and Operating Conditions
Parameter Reference Rated Extreme
Transportation
and Storage
Ambient Temp.
°F
°C
77 ± 5
25 ± 3
32 to 131
0 to 55
32 to 140
0 to 60
–40 to 151
–40 to 66
Ambient Relative
Humidity *
10 % to 55 % RH
non-condensing
10 % to 90 % RH
non-condensing
5 % to 90 % RH
non-condensing
5 % to 95 % RH
non-condensing
Mechanical
Acceleration
Duration
0 g
0 ms
1 g
30 ms
5 g
30 ms
20 g
30 ms
Vibration
10 Hz to 60 Hz—
amplitude 0.07 mm
(peak-to-peak)
0 Hz to 14 Hz—amplitude
2.5 mm (peak-to-peak)
60 Hz to 150 Hz—
acceleration 1 g
14 Hz to 250 Hz—
acceleration 1 g
Power
Voltage
Frequency
Power Consumption
100 V to 240 V (24 V
optional)
50/60 Hz
110 VA typical 115VAC
*Relative Humidity is de-rated above 40 °C.
Module “T” Rating for Class 1, Div. 2, groups A, B, C, D
Analog Input Module – 8 channel
T6
Digital Input, Contact type, 16 channel
T5
Digital Input, 24Vdc type, 16 channel
T4
Digital Input, 120/240 Vac, 16 channel
T3C @ Ta=60°C
T4 @ Ta=40°C
Analog Output, 4 channel
T5
Digital Output, Relay type, 8 channel
T5
Digital Output, 24Vdc, 16 channel
T4
Digital Output, 120/240Vac, 8 channel
T4