Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output
202 HC900 Hybrid Controller Installation and User Guide Revision 5
9/03
8 Point AC Digital Output
Step Action
2 Mount RTP to DIN rail.
Latch to rail. See page 205.
Connect cable to RTP
3 Set/verify jumper positions as shown.
Jumper open
Jumper closed
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. Please see page 62 for more details.
See page 203 for RTP internal schematic.
4 Connect field wiring.
Note: S-L1 in the wiring figure below refers to power that is disconnected from these screw terminals when
switch SW1 is open (0).