Marley
/
MD Cooling Tower
/
Engineering Data : Schematic
19
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H A Weight/Cell
Heaviest
Section
MD5016PAC4L
11 79
4801 3091 5933 3353 1710
MD5016PLC4L 320 11 78
MD5016QAC4L 345 15 80
MD5016QLC4L 348 15 79
MD5016RAC4L 369 18.5 80
MD5016RLC4L 372 18.5 79
MD5016SAC4L 390 22 81
MD5016SLC4L 394 22 80
MD5016PAD4L 350 11 79
5106 3396 6217 3636 1874
MD5016PLD4L 353 11 78
MD5016QAD4L 383 15 80
MD5016QLD4L 384 15 79
MD5016RAD4L 410 18.5 80
MD5016RLD4L 412 18.5 79
MD5016SAD4L 436 22 81
MD5016SLD4L 437 22 80
MD5016TAD4L 475 30 82
MD5016TLD4L 471 30 80
MD5016PAF4L 368 11 79
5410 3701 6448 3868 2105
MD5016PLF4L 370 11 78
MD5016QAF4L 403 15 80
MD5016QLF4L 401 15 79
MD5016RAF4L 431 18.5 80
MD5016RLF4L 431 18.5 79
MD5016SAF4L 460 22 81
MD5016SLF4L 459 22 80
MD5016TAF4L 500 30 82
MD5016TLF4L 493 30 80
MD5016 FOUR OR MORE CELLS