A SERVICE OF

logo

Marley
/
MD Cooling Tower
/
Engineering Data : Schematic
7
NOTE
1 Use this bulletin for preliminary layouts only. Obtain
current drawings from your Marley sales representative. All
table data is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H A Weight/Cell
Heaviest
Section
MD5008MAC1L
165
5.5 80
3294 2181 3051 1702 891
MD5008MLC1L 163 5.5 79
MD5008NAC1L 179 7.5 81
MD5008NLC1L 179 7.5 79
MD5008PAC1L 202 11 81
MD5008PLC1L 202 11 80
MD5008QAC1L 216 15 81
MD5008QLC1L 216 15 80
MD5008MAD1L 180 5.5 80
3599 2486 3176 1828 936
MD5008MLD1L 177 5.5 79
MD5008NAD1L 197 7.5 81
MD5008NLD1L 196 7.5 79
MD5008PAD1L 223 11 81
MD5008PLD1L 223 11 80
MD5008QAD1L 239 15 81
MD5008QLD1L 238 15 80
MD5008MAF1L 189 5.5 80
3904 2791 3302 1953 1062
MD5008MLF1L 185 5.5 79
MD5008NAF1L 207 7.5 81
MD5008NLF1L 206 7.5 79
MD5008PAF1L 234 11 81
MD5008PLF1L 234 11 80
MD5008QAF1L 255 15 81
MD5008QLF1L 257 15 80
MD5008 SINGLE CELL