A SERVICE OF

logo

Marley
/
MD Cooling Tower
/
Engineering Data : Hoisting
25
Model
Base Module Top Module
Width
Sling Length
Minimum
Weight
kg
Width
Sling Length
Minimum
Weight
kg
MD5008 2.6m 3m 1100 2.8m 3m 900
MD5010 2.6m 4m 1350 2.6m 3m 1050
MD5016 3.7m 4m 1650 3.7m 3m 1750
1 Hoisting operations can be dangerous and suitable safety
precautions should be taken to protect personnel and the
equipment being hoisted.
2 All hoisting equipment should be certified and comply with
local and national safety regulations.
NOTE
3 Ensure that slings are of sufficient length so not to impose
bending loads onto the casing—use of spreader bars is
essential.
4 For overhead lifts or where additional safety is required, add
slings beneath the tower unit
OFFSET MAY BE REQUIRED
FOR BALANCED LIFT
CENTER OF
TOWER
CENTER OF
TOWER
WIDTH
WIDTH
LIFTING
SLING
LIFTING
SLING
70° MAX
BOTH MODULES
OFFSET MAY BE REQUIRED
FOR BALANCED LIFT