A SERVICE OF

logo

Marley
/
MD Cooling Tower
/
Engineering Data : Outlet Connection
24
A
B
C
D
C
L
TOWER
PUMP
SUCTION
MAKEUP
2" NPTM
MAKEUP
ALTERNATE LOCATION
OVERFLOW
3" NPTF
89
SUCTION HOOD
WELDING
BEVEL
MECHANICAL
COUPLING GROOVE
REMOVABLE
TRASH SCREEN
23
DRAIN
3" NPTF
SIDE-OUTLET SUCTION CONNECTION
END-OUTLET SUCTION CONNECTION
SIDE-OUTLET SUMP CONNECTION
SUCTION SECTION
SUMP SECTION
BOTTOM OUTLET
CONNECTION
B
C
L
TOWER
C
L
SUMP
SUMP FACE MAY
BE ROTATED 90° OR 180°
MAKEUP
2" NPTM
MAKEUP
ALTERNATE LOCATION
OVERFLOW
3" NPTF
153
502
ANTI-VOTEX PLATE
WITH SCREEN OR
REMOVABLE
TRASH SCREEN
DRAIN
3" NPTF
DRAIN
1
1
/2" NPTF
OUTLET PIPING
BY OTHERS
C
L
OUTLET
C
D
89
Model
Dimensions
Suction
Diameter
A B C D
MD5008
6" 493 588 305
8" 191 493 588 305
10" 493 588 305
MD5010
6" 477 588 305
8" 191 477 588 305
10" 477 588 305
MD5016
6" 477 639 331
8" 191 477 639 331
10" 216 477 639 331
12" 477 639 331
Maximum m
3
/hr per Outlet
Outlet
Diameter
Side or End Suction
pump flow
Sump
pump flow
without
anti-vortex plate
Sump
pump flow
with anti-vortex plate or
gravity flow
with or without
anti-vortex plate
Bottom Outlet
pump flow
without
anti-vortex plate
Bottom Outlet
plump flow
with anti-vortex plate or
gravity flow
with or without
anti-vortex plate
MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 MD5008 MD5010 MD5016
6" 144 144 144 205 205 205 76
8" 259 338 355 248 248 248 259 338 355 136 136 136
10" 493 259 338 391 259 338 493 96 101 215 215 215
12" 493 493 142 143 143 259 304 304
14" 173 173 173 259 338 368
16" 226 226 226 259 338 480
18" 259 286 286 259 338 493
20" 338 355 338 493
24" 493 493
A
C
D
PUMP
SUCTION
MAKEUP
2" NPTM
OVERFLOW
3" NPTF
89
496
878
SLOPING
BASIN FLOOR
DRAIN
3" NPTF