Table 39. Sensor Voltage (Vdc) Versus Pressure (Inw).
Fig. 64. Graph of Sensor Voltage (Vdc) versus Pressure
(Inw).
L
ON
, Neuron
, and L
ON
W
ORKS
are registered trademarks
of Echelon
Corporation. L
ON
M
ARK
and L
ON
M
ARK
logo are
registered trademarks of the L
ON
M
ARK
Interoperability
Association.
Pressure Inw (kPa) Sensor Voltage (Vdc)
0.00
0.00
2.00
0.50.
0.13
2.80
1.00
0.25
3.60
1.50
0.37
4.40
2.00
0.5
5.20
2.50
0.62
6.00
3.00
0.75
6.80
3.50
0.87
7.60
4.00
1.00
8.40
4.50
1.12
9.20
5.00
1.25
10.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
0 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00
VOLTS (VDC)
INW
SENSOR VOLTAGE VERSUS PRESSURE
M11606