EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—128
NOTE: Durin
all modes all di
ital and analo
ph
sical
inputs are periodicall
read, the dia
nostic output
network variables can be polled, the input network
variables are received, and the output network
variables are sent periodicall
.
UNOCCUPIED
Controller occupanc
mode was
overridden to Unoccupied mode
Network input
DestManOcc
containin
a time-of-da
schedule
override si
nal of UNOCCUPIED from the Excel 10 Zone Mana
er or
other L
ON
W
ORKS
Bus device.
BYPASS
Controller occupanc
mode was
overridden to B
pass the current
Unoccupied mode
DI
B
pass
was pressed, and the B
pass duration timer has not
et
expired, or the network input DestManOcc has a value of BYPASS.
NOT
ASSIGNED
No B
pass action No Override input received.
Operational Modes (User Address: StatusMode)
START-UP
AND WAIT
On power-up, provides a sta
ered
start se
uence to evenl
appl
the load
to the electrical s
stem.
This mode occurs on controller power-up, and after downloadin
to the
controller from the confi
uration tool. Temperature control loops are
disabled.
COOLING
The Excel 10 is controllin
the Coolin
mode.
Space temperature has risen above the current coolin
setpoint, or the
network input
DestHvacMode
is COOL.
HEATING
The Excel 10 is controllin
the Heatin
mode.
Space temperature has fallen below the current heatin
setpoint, or the
network input
DestHvacMode
is HEAT.
EMERGENCY
HEAT
Compressors are disabled and onl
Auxiliar
Heat sta
es are allowed to
operate.
The network input
DestManHvacMode
is EMERG_HEAT.
OFF MODE
The heat/cool control is turned off
immediatel
. The node is not runnin
its
normal temperature control.
Network input
DestManMode
containin
AHU operational mode
information from C-Bus has value of MORNING WARM-UP.
DISABLED
MODE
The heat/cool control and frost
protection are turned off immediatel
.
The node is not runnin
its normal
temperature control.
–
SMOKE
EMERGENCY
The node has entered a smoke
emer
enc
. The fan and dampers are
then set to the conditions confi
ured b
SmkCtlMode. The control remains in
SMOKE_ EMERGENCY until power is
c
cled or the node receives
DestEmer
Cmd set to
EMERG_NORMAL.
Network input
DestEmer
Cmd
containin
smoke control si
nal from
another L
ON
W
ORKS
Bus device has value of SMOKE_EMERG.
FREEZE
PROTECT
The temperature control is set to HEAT
with the setpoint set to the frost limit
setpoint 46.4°F
8°C
.
The Window di
ital input detects an open window.
MANUAL
POSITION
The ph
sical outputs are bein
controlled manuall
. The temperature
control loop is turned off.
T
picall
this is done b
the user throu
h E-Vision or XBS b
settin
the point DestManMode to MANUAL mode.
FAN ONLY
Control al
orithm is disabled, except
that the fan is turned on.
The space temperature sensor has failed, or the network input
DestHvacMode
is FAN ONLY.
DISABLED
Control al
orithm is shut off. Network input
DestManMode
containin
AHU operational mode
information from an operator or the network that has a value of
DISABLED.
Table 5. Modes Of Operation For The Excel 10 W7750 Controller (Continued).
Mode Description Events causing a controller to switch to this mode