EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
53 74-2958—1
Common Operations
The Excel 10 W7750 Controller applications have man
common operations that are applicable re
ardless of the t
pe
of heatin
, coolin
, or economizer e
uipment confi
uration.
These operations are available to the W7750A and the
W7750B,C Versions of the CVAHU Controller, and the I/O and
network confi
urations for them are summarized in Table 14.
Available input options are from the wall module and the
hard-wired analo
and di
ital inputs. Each application can
have onl
a subset of these devices confi
ured based on the
number of ph
sical I/O points available. However, some of the
inputs are available over the L
ON
W
ORKS
Bus network.
NOTE: Each W7750 Controller
must
have a space
temperature sensor input either wired directl
to the
controller, or shared from another L
ON
W
ORKS
Bus
device, and must have a di
ital output confi
ured for
controllin
the suppl
fan. In addition, if modulatin
economizer control is desired, a dischar
e air
temperature sensor
must
be ph
sicall
connected to
the Excel 10 W7750 Controller. A dischar
e
temperature si
nal
cannot
be brou
ht into the
controller throu
h the L
ON
W
ORKS
Bus network.
Table 14. Common Configuration Options Summary For W7750A,B,C Controllers.
Option Possible Configurations Common To All W7750 Models
Supply Fan
1. Mandator
Di
ital Output.
Type of Air Handler
1. Conventional.
2. Heat Pump.
Occupancy Sensor
1. None.
2. Connected: Contacts closed e
uals Occupied.
3. Network
Occ/Unocc si
nal received via the L
ON
W
ORKS
Bus network
.
Window Sensor
1. None.
2. Ph
sicall
Connected: Contacts closed e
uals window closed.
3. Network
Window Open/Closed si
nal received via the L
ON
W
ORKS
Bus
.
Wall Module Option
1. Local
direct wired to the controller
.
The T77560A,B has no L
ON
W
ORKS
Bus access
2. Network
sensor value received via the L
ON
W
ORKS
Bus
.
Wall Module Type
1. Sensor onl
.
All wall modules have a L
ON
W
ORKS
Bus access 2. Sensor and Setpoint ad
ust.
ack except T7560A,B
3. Sensor, Setpoint ad
ust and B
pass.
4. Sensor and B
pass.
Smoke Emergency
Initiation
1. None.
2. Ph
sicall
Connected: Contacts closed e
uals smoke detected.
3. Network
Emer
enc
/Normal si
nal received via the L
ON
W
ORKS
Bus
.