EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—148
Step 6. Configure Controllers
Excel E-Vision PC Software is used to confi
ure W7750
Controllers to match their intended application. The E-Vision
User Guide, form number 74-2588 provides details for
operatin
the PC software.
W7750 Controllers are shipped from the factor
with a default
hardware confi
uration. On power-up, the controller
confi
uration parameters are set to the default values listed in
Table 20 in Appendix C. The controller can operate normall
in this mode
if the e
uipment and wirin
match the default
setup
, and
iven valid sensor inputs, the outputs are
controlled appropriatel
to maintain space temperature at the
default setpoint. The default I/O arran
ement for the W7750A
is printed on the terminal labels. Also see the wirin
details in
Fi
. 27 in Step 4, Prepare Wirin
Dia
rams. The labeled I/O
terminals are defined in Table 10.
Step 7. Troubleshooting
Troubleshooting Excel 10 Controllers and Wall
Modules
In addition to the followin
information, refer to the Installation
Instructions and Checkout and Test manual for each product.
Most products have a Checkout and Test section in their
Installation Instructions manual. If not, look for a separate
Checkout and Test manual. See the Applicable Literature
section for form numbers.
ML6464A1009 Direct Coupled Actuator, 66 lb-in. tor
ue,
Series 60
—
ML6474A1008 Direct Coupled Actuator, 132 lb-in. tor
ue,
Series 60
—
ML6185A1000 Direct Coupled Actuator, 50 lb-in. sprin
return Series 60
V5852A/V5862A Two-wa
terminal unit water valve; 0.19, 0.29,
0.47, 0.74, 1.2, and 1.9 C
v
1/2 in. npt
13 mm
or 2.9 and 4.9 C
v
3/4 in. npt
19 mm
Use with M6410 Valve Actuator. Close-off ratin
for 0.19 to 1.9 C
v
is 65 psi; for 2.9 and 4.9, C
v
is
45 psi.
Coefficient of volume or capacit
index
C
v
=
allons per minute divided b
the s
uare
root of the pressure drop across the valve.
V5853A/V5863A Three-wa
mixin
terminal unit hot water valve;
0.19, 0.29, 0.47, 0.74, 1.2, and 1.9 C
v
1/2 in.
npt
13 mm
or 2.9 and 4.9 C
v
3/4 in. npt
19
mm
Use with M6410 Valve Actuator. Close-off ratin
for 0.19 to 0.74 C
v
is 55 psi; 1.2 and 1.9 C
v
is 22
psi; 2.9 and 4.9 C
v
is 26 psi.
R8242A Contactor, 24 Vac coil, DPDT —
AT72D, AT88A, AK3310, etc. Transformers —
EN 50 022 DIN rail 35 mm b
7.5 mm
1-3/8 in. b
5/16 in.
Obtain locall
: Each controller re
uires 5 in.
— Two DIN rail adapters Obtain locall
: Part number TKAD, from Thomas
and Betts, two for each controller.
Cabling:
— Serial Interface Cable, male DB-9 to female
DB-9 or female DB-25.
Obtain locall
from an
computer hardware
vendor.
Hone
well
AK3791
one twisted pair
AK3792
two twisted pairs
L
ON
W
ORKS
Bus
plenum
: 22 AWG
0.34 mm
2
twisted pair solid conductor, nonshielded or
Echelon approved cable.
Level IV 140°F
60°C
ratin
Hone
well AK3781
one
twisted pair
AK3782
two
twisted pairs
L
ON
W
ORKS
Bus
nonplenum
: 22 AWG
0.34
mm
2
twisted pair solid conductor, nonshielded
or Echelon approved cable.
Level IV 140°F
60°C
ratin
Hone
well AK3725
Inputs: 18 AWG
1.0 mm
2
five wire cable
bundle
Standard thermostat wire
Hone
well AK3752
t
pical or
e
uivalent
Outputs/Power: 14 to 18 AWG
2.0 to 1.0 mm
2
NEC Class 2 140°F
60°C
ratin
Hone
well AK3702
t
pical or
e
uivalent
18 AWG
1.0 mm
2
twisted pair
Non-plenum
Hone
well AK3712
t
pical or
e
uivalent
16 AWG
1.3 mm
2
twisted pair
Non-plenum
Hone
well AK3754
t
pical or
e
uivalent
14 AWG
2.0 mm
2
two conductor
Non-plenum
Table 11. Excel 10 W7750 Controller Ordering Information. (Continued)
Part Number Product Description Comments