EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
37 74-2958—1
Table 10. W7750A Version I/O Description.
IMPORTANT
If the W7750A controller is configured by E-Vision,
the outputs may be assigned in different order than
the factory defaults. Use the Custom Wiring function
of E-Vision to re-assign the outputs to the desired
terminals.
The W7750B,C Versions are preconfi
ured with the same
factor
default setup as the W7750A Model; however, some
terminals for wirin
connections differ on the W7750B,C
Models. See Fi
. 30 for the terminal names on the W7750B
Model and Fi
. 35 for the terminal names on the W7750C
Model. The factor
default confi
uration of the di
ital output
points on the W7750B,C Models follow
terminal names are
from the W7750A
:
FACTORY DEFAULT DIGITAL OUTPUTS:
FREE 1
OUT 1
DO1—NETWORK DO
OUT 2
DO2—SUPPLY FAN START/STOP
OUT 3
DO3—COOL_STAGE_2
OUT 4
DO4—COOL_STAGE_1
OUT 5
DO5—HEAT_STAGE_2
OUT 6
DO6—HEAT_STAGE_1
DO7—UNUSED
DO8—UNUSED
The Wall Module terminals are identical for the W7750A,B,C
Models.
The W7750B,C Models offers two volta
e/current sensor
input terminals. When current-t
pe sensors
4 to 20 mA
are
confi
ured, the W7750B,C automaticall
switches a 249 ohm
resistor into the sensin
circuit; so no external resistor is
re
uired. The W7750A Model does not support volta
e or
current inputs.
NOTE: If usin
factor
defaults, DI-2 input is confi
ured for
ScheduleMaster
nvoIO.SchedMaster
. For a
stand-alone unit, either connect an external time
clock to terminals 9 and 10 or put a
umper on
terminals 9 and 10
usin
a
umper puts the
controller in continuous occupied mode
.
Terminal Terminal Number Description
DO6–
W1
31 Heat 1
or Reversin
Valve for a Heat Pump
DO5–
W2
30 Heat 2
or Aux. Heat for a Heat Pump
DO4–
Y1
29 Cool 1
or Compressor 1 for a Heat Pump
DO3–
Y2
28 Cool 2
or Compressor 2 for a Heat Pump
DO2–
G
27 Fan
DO1–NET 26 Network Di
ital Output
DO1–NET 25 Network Di
ital Output
connect to terminal number 22 +24Vac
Rc 24 Control power for rela
contacts DO2
G
, DO3
Y1
and DO4
Y2
Rh 23 Control power for rela
contacts DO5
W1
and DO6
W2
+24Vac
H
22 Power for the controller
COM
N
21 Return for power to controller
E-Bus 14 and 15 Echelon communications
L
ON
W
ORKS
Bus
screw terminals
DI - 2 12 Di
ital Input 2
DGND 11 Di
ital Ground
DGND 10 Di
ital Ground
DI - 1 9 Di
ital Input 1
AGND 8 Analo
round
AI - 1 OHM 7 Analo
Input 1
used for Dischar
e Air Temperature Sensor
SET PT 6 Space temperature setpoint potentiometer
GROUND 5 Wall Module
SENSOR 4 Space temperature sensor
BYPASS 3 Space override button
LED 2 Space LED for indication of manual occupanc
status
EARTH GND 1 Earth Ground