A SERVICE OF

logo

KeypadLinc Schedule Timer Owner’s Manual
Page 8 of 26
Using KeypadLinc Schedule Timer in Virtual Multi-Way Circuits
Once KeypadLincs have been installed, you can create a virtual multi-way circuit to control a single load.
Rather than connect each switch directly to the load, virtual multi-ways use INSTEON messaging to
control the load. Two components make up a virtual multi-way circuit:
KeypadLinc Primary wired directly to the load
KeypadLinc Secondaries other KeypadLincs in the circuit, but not wired to the load
The diagram below shows how to wire a 3-way circuit with two KeypadLincs. After the KeypadLincs have
been wired-in, you create a virtual multi-way by Cross-Linking each of the desired KeypadLincs to one
another (see Cross-Linking INSTEON Devices).
NOTE: Actual location of the wires on KeypadLinc may differ with device revision or model.
The KeypadLinc Primary’s LOAD wire gets connected to the actual load that is being controlled
The LOAD wire for any KeypadLinc Secondaries will not be connected to anything, so cap those
LOAD wires off with a wire nut
Notice that one of the TRAVELER wires (TRAVELER 1, the red one) is not used, so you will cap it off
at both ends with a wire nut. The other TRAVELER (TRAVELER 2, the black one) you will convert to
a LINE wire. In the junction box where the KeypadLinc Secondary is, connect TRAVELER 2 to the
existing LINE and also to the KeypadLinc Secondary’s LINE wire. In the junction box at the other end,
you will connect TRAVELER 2 to the KeypadLinc Primary’s LINE wire.
All KeypadLincs, whether they are Primaries or Secondaries, must be connected to NEUTRAL and to
GROUND. Note that the switches you are replacing will not normally have a connection to NEUTRAL.
If there is no NEUTRAL wire in the junction box, please consult an electrician or call INSTEON Gold
Support Line at 800-762-7845.
KeypadLinc
Primary
KeypadLinc
Secondary