Page 11
Cumberland Gap Wood Stove
R
November 5, 2010
7006-188G
FLOOR PROTECTOR: Floor protector must be non-
combustible material, extending beneath heater and to the
front/sides/rear as indicated. The fl oor must be a minimum
of 1/2 inch (26mm) thickness ("k" value = 0.84, R value =
0.59) non-combustible or otherwise adequately protected
from radiant heat given off by the unit and from sparks and
falling embers. A layer of thin brick or ceramic tile over a
combustible fl oor is not suffi cient. See Alternate Floor Pro-
tection on page 12.
CANADA
200mm (8")
200mm
(8")
450mm (18")
1371mm
(54")
Minimum
1089mm (42-7/8") Minimum
200mm
(8")
SIDE FUEL DOOR LOCKED SHUT
BOTH FUEL DOORS ACCESSIBLE
16" (406mm) from
fuel loading door
8"
(200mm)
USA
Front Fuel
loading door
34-5/8"(879mm)
Minimum
39-1/8"
(994mm)
Minimum
See page 6 for stove clearances
In USA installations, it is necessary to install a non-
combustible fl oor protector at least 16 inches in front and 8
inches to both sides of the fuel loading doors. See *excep-
tion below.
In Canada, similar fl oor protection must be provided 18
inches (450mm) in front and 8 inches (200mm) from the
sides and rear of the stove. See *exception below.
*EXCEPTION: Non-combustible fl oor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
4
Installation Considerations
A. Hearth Protection Requirements
Figure 11.1
Figure 11.2
Figure 11.3
Figure 11.4