32
Table 9 — Service Test Mode and Sub-Mode Directory
LEGEND
EXV — Electronic Expansion Valve
SUB-MODE
KEYPAD
ENTRY
ITEM RANGE ITEM EXPANSION COMMENT
TEST TEST OFF-ON SERVICE TEST MODE Use to Enable/Disable Manual Mode
OUTS
LLS.A OPEN-CLSE LIQ. LINE SOLENOID VALVE TXV units only
EXV.A 0 - 100% EXV % OPEN
LLS.B OPEN-CLSE LIQ. LINE SOLENOID VALVE TXV units only
EXV.B 0 - 100% EXV % OPEN
FAN1 OFF-ON FAN 1 RELAY Fan 3:
(040-050)
Fans 3, 4:
(060-110, 230B-315B)
Fans 1, 2:
(130 [60 Hz])
Fans 1:
(130 [50 Hz], 150, 170,
230A-270A, 330A/B, 360B [50 Hz])
Fans 1, 11: (190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
FAN2 OFF-ON FAN 2 RELAY Fan 4:
(040-050)
Fans 5, 6: (060-090, 230B-245B)
Fans 5, 6, 7, 8:
(100, 110, 255B-315B)
Fans 3, 4, 9, 10:
(130 [60 Hz])
Fan 2: (130 [50 Hz], 150, 170,
230A-270A, 330A/B, 360B [50 Hz])
Fans 2, 12:
(190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
FAN3 OFF-ON FAN 3 RELAY
Fans 3, 9:
(130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)
FAN4 OFF-ON FAN 4 RELAY
Fans 4, 10:
(130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)
CLR.P OFF-ON COOLER PUMP RELAY
CND.P OFF-ON CONDENSER PUMP RELAY
RMT.A OFF-ON REMOTE ALARM RELAY
COMP
CC.A1 OFF-ON COMPRESSOR A1 RELAY
CC.A2 OFF-ON COMPRESSOR A2 RELAY
CC.A3 OFF-ON COMPRESSOR A3 RELAY
CC.A4 OFF-ON COMPRESSOR A4 RELAY
UL.A1 OFF-ON UNLOADER A1 RELAY
UL.A2 OFF-ON UNLOADER A2 RELAY
HGBP OFF-ON HOT GAS BYPASS RELAY
CC.B1 OFF-ON COMPRESSOR B1 RELAY
CC.B2 OFF-ON COMPRESSOR B2 RELAY
CC.B3 OFF-ON COMPRESSOR B3 RELAY
CC.B4 OFF-ON COMPRESSOR B4 RELAY
UL.B1 OFF-ON UNLOADER B1 RELAY
UL.B2 OFF-ON UNLOADER B2 RELAY
ENTER
ENTER
ENTER