34
Table 13 — Reading and Changing Chilled Fluid Set Point
Table 14 — Inputs Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY RANGE ITEM EXPANSION COMMENT
COOL
CSP.1 44.0 °F –20-70 F COOLING SETPOINT 1
Default: 44 F
38-70 F Flud = 1
14-70 F Flud = 2
–20-70 F Flud = 3
44.0 °F –20-70 F Scrolling stops
44.0 °F –20-70 F Value flashes
–20-70 F Select 46.0
46.0 °F –20-70 F Change accepted
CSP.1 46.0 °F –20-70 F COOLING SETPOINT 1 Item/Value/Units scrolls again
SUB-MODE
KEYPAD
ENTRY
ITEM RANGE ITEM EXPANSION COMMENT
GEN.I
STST STRT-STOP START/STOP SWITCH
Enable/Off/Remote
Contact Switch Input
FLOW OFF-ON COOLER FLOW SWITCH
CND.F OFF-ON CONDENSER FLOW SWITCH
DLS1 OFF-ON DEMAND LIMIT SWITCH 1
DLS2 OFF-ON DEMAND LIMIT SWITCH 2
ICED OFF-ON ICE DONE
DUAL OFF-ON DUAL SETPOINT SWITCH
CRCT
FKA1 OFF-ON COMPRESSOR A1 FEEDBACK
FKA2 OFF-ON COMPRESSOR A2 FEEDBACK
FKA3 OFF-ON COMPRESSOR A3 FEEDBACK
FKA4 OFF-ON COMPRESSOR A4 FEEDBACK
OIL.A OPEN-CLSE OIL PRESSURE SWITCH A
LPS.A OPEN-CLSE LOW PRESSURE SWITCH Not applicable (040-420)
FKB1 OFF-ON COMPRESSOR B1 FEEDBACK
FKB2 OFF-ON COMPRESSOR B2 FEEDBACK
FKB3 OFF-ON COMPRESSOR B3 FEEDBACK
FKB4 OFF-ON COMPRESSOR B4 FEEDBACK
OIL.B OPEN-CLSE OIL PRESSURE SWITCH B
LPS.B OPEN-CLSE LOW PRESSURE SWITCH Not applicable (040-420)
4-20
DMND 0 - 24 mA 4-20 mA DEMAND SIGNAL
RSET 0 - 24 mA 4-20 mA RESET SIGNAL
CSP 0 - 24 mA 4-20 mA COOLING SETPOINT
HSP 0 - 24 mA 4-20 mA HEATING SETPOINT
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER