Table 16 — Configuration Mode and Sub-Mode Directory (cont)
LEGEND
SUB-MODE
KEYPAD
ENTRY
ITEM
MARQUEE
DISPLAY RANGE
NAVIGATOR
DISPLAY RANGE
ITEM EXPANSION COMMENT
UNIT TYPE 1 - 5
AIR COOLED
WATER COOLED
SPLIT
HEAT MACHINE
HEAT RECLAIM
UNIT TYPE Default: 1
1 = Air Cooled
2 = Water Cooled
3 = Split System
4 = Heat Machine
5 = Heat Reclaim
TONS 15 - 300 15 - 300 UNIT SIZE
CAP.A 0 - 100% 0 - 100% CIRCUIT A % CAPACITY
CMP.A 1 - 4 1 - 4 NUMBER CIRC A COMPRESSOR
CYL.A 4, 6 4, 6 COMPRESSOR A1 CYLINDERS
CMP.B 1 - 4 1 - 4 NUMBER CIRC B COMPRESSOR
CYL.B 4, 6 4, 6 COMPRESSOR B1 CYLINDERS
EXV NO-YES NO-YES EXV MODULE INSTALLED
SH.SP
10 - 40
∆
F
(6 - 22
∆
C)
10 - 40
∆
F
(6 - 22
∆
C)
EXV SUPERHEAT SETPOINT
Default
29 = 30GTN,R
23 = 30GUN,R
SH.OF
–20 - 20
∆
F
(–11 - 11
∆
C)
–20 - 20
∆
F
(–11 - 11
∆
C)
EXV SUPERHEAT OFFSET Default: 0
REFG 1, 2 1, 2 REFRIGERANT
1 = R-22 (30GTN,R)
2 = R-134a (30GUN,R)
FAN.S 1 - 4
2 STAGE IND
3 STAGE IND
2 STAGE COM
3 STAGE CO
M
FAN STAGING SELECT 1 = 2 Stage Independent
2 = 3 Stage Independent
3 = 2 Stage Common
4 = 3 Stage Common (Not supported
for air cooled)
OPT1
FLUD 1 - 3 1 - 3 COOLER FLUID 1 = Water
2 = Med. Brine
3 = Low Brine
HGB.S NO-YES NO-YES HOT GAS BYPASS SELECT
HPCM 1 - 4
EXV CONTROL
SETPOINT CONTROL
SET A EXV B
EXV A SET B
HEAD PRESS. CONT. METHOD Default:2
1 = EXV Control
2 = Set Point Control
3 = Set Point Circuit A, EXV Circuit B
4 = Set Point Circuit B, EXV Circuit A
HPCT 0 - 2
NO CONTROL
AIR COOLED
WATER COOLED
HEAD PRESS. CONTROL TYPE Default: 1
0 = No Control
1 = Air Cooled
2 = Water Cooled
MMR.S NO-YES NO-YES MOTORMASTER SELECT
PRTS NO-YES NO-YES
PRESSURE
TRANSDUCERS
Default: NO
Not Supported
PMP.I OFF-ON OFF-ON COOLER PUMP INTERLOCK Default: ON
CPC OFF-ON OFF-ON COOLER PUMP CONTROL Default: OFF
CNP.I OFF-ON OFF-ON CONDENSER PUMP INTERLOCK
Default: OFF
Not Applicable
CNPC 0 - 2 NO CONTROL
ON WITH MODE
ON WITH COMP
CONDENSER PUMP CONTROL Default: 0
0 = Not Controlled
1 = On with Occupied Mode
2 = On with Compressors
CWT.S NO-YES NO-YES CONDENSER FLUID SENSORS
Default: NO
Not Applicable
CA.UN 0 - 2 0 - 2 NO. CIRCUIT A UNLOADERS
CB.UN 0 - 2 0 - 2 NO. CIRCUIT B UNLOADERS
EMM NO-YES NO-YES EMM MODULE INSTALLED
OPT2
CTRL 0 - 3 SWITCH
7 DAY OCC
OCCUPANCY
CCN
CONTROL METHOD 0 = Switch
1 = 7-Day Schedule
2 = Occupancy Schedule
3 = CCN
CCNA 1 - 239 1 - 239 CCN ADDRESS Default: 1
CCNB 0 - 239 0 - 239 CCN BUS NUMBER Default: 0
CCN — Carrier Comfort Network
EMM — Energy Management Module
EXV — Electronic Expansion Valve