CL-4
C. Unit Start-Up (cont)
UNIT (Configuration Settings)
PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’.
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
OPTIONS1 (Options Configuration)
ITEM DESCRIPTION STATUS UNITS VALUE
TYPE
Unit Type 1 = Air Cooled
2 = Water Cooled
3 = Split System
4 = Heat Machine
5 = Air Cooled Heat Reclaim
TONS
Unit Size 15 to 300 TONS
CAP.A
Circuit A1% Capacity 0 to 100 %
CMP.A
Number Circ A Compressor 1 to 4
CYL.A
Compressor A1 Cylinders 4 or 6
CMP.B
Number Circ B Compressor 1 to 4
CYL.B
Compressor B1 Cylinders 4 or 6
EXV
EXV Module Installed No/Yes
SH.SP
EXV Superheat Setpoint 10 to 40 ^F
SH.OF
EXV Superheat Offset –20 to 20 ^F
REFG
Refrigerant 1 = R22 2 = R134A
FAN.S
Fan Staging Select 1 = 2 Stage indpt.
2 = 3 Stage indpt.
3 = 2 Stage common
4 = 3 Stage common
ITEM DESCRIPTION STATUS VALUE
FLUD
Cooler Fluid 1 = Water
2 = Med. Brine
3 = Low Brine
HGB.S
Hot Gas Bypass Select No/Yes
HPCM
Head Press. Cont. Method 1 = EXV controlled
2 = Setpoint controlled
3 = Setpoint-A, EXV-B
4 = EXV-A, Setpoint-B
HPCT
Head Press. Control Type 0 = None
1 = Air Cooled
2 = Water Cooled
MMR.S
Motormaster Select No/Yes
PRTS
Pressure Transducer No/Yes
PMP.I
Cooler Pump Interlock Off/On
CPC
Cooler Pump Control Off/On
CNP.I
Condenser Pump Interlock Off/On
CNPC
Condenser Pump Control 0 = No Control
1 = On with Mode
2 = On with Compressor(s)
CWT.S
Condenser Fluid Sensors No/Yes
CA.UN
No. Circuit A Unloaders 0-2
CB.UN
No. Circuit B Unloaders 0-2
EMM
EMM Module Installed No/Yes