C. Unit Start-Up (cont)
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY DISP.
PRESS ENTER AGAIN TO DISPLAY TEST FOLLOWED BY OFF. PRESS ENTER TO STOP DISPLAY AT
OFF AND ENTER AGAIN SO OFF DISPLAY FLASHES. PASS AND WORD WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING OFF DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ON AND PRESS ENTER. ALL LED
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO
RETURN TO THE DISP DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY TEST. PRESS ENTER TO STOP DISPLAY
AT OFF AND ENTER AGAIN SO OFF FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS TEST ON.
PRESS THE DOWN ARROW TO DISPLAY OUTS. PRESS THE ENTER KEY TO DISPLAY LLS.A. PRESS
THE ENTER KEY TO STOP DISPLAY AT OFF AND ENTER AGAIN SO OFF FLASHES. PRESS THE UP
ARROW KEY AND ENTER TO TURN THE OUTPUT ON. PRESS ENTER SO THE ON DISPLAY FLASHES,
PRESS THE DOWN ARROW KEY AND THEN ENTER TO TURN THE OUTPUT OFF. OUTPUTS WILL ALSO BE
TURNED OFF OR SENT TO 0% WHEN ANOTHER OUTPUT IS TURNED ON. CHECK OFF THE FOLLOWING
THAT APPLY AFTER BEING TESTED:
USE ESCAPE KEY TO RETURN TO OUTS DISPLAY. PRESS DOWN ARROW TO DISPLAY COMP. PRESS
ENTER KEY TO DISPLAY CC.A1. NOTE THAT UNLOADERS AND HOT GAS BYPASS SOLENOIDS CAN BE
TESTED BOTH WITH AND WITHOUT COMPRESSOR(S) RUNNING. MAKE SURE ALL SERVICE VALVES ARE
OPEN AND COOLER/CONDENSER PUMPS HAVE BEEN TURNED ON BEFORE STARTING COMPRES-
SORS. CHECK OFF EACH ITEM AFTER SUCCESSFUL TEST. THE CONTROL WILL ONLY START ONE COM-
PRESSOR PER MINUTE. WHEN AT THE DESIRED ITEM, PRESS THE ENTER KEY TWICE TO MAKE THE
OFF FLASH. PRESS THE UP ARROW KEY AND ENTER TO TURN THE OUTPUT ON.
CHECK AND ADJUST SUPERHEAT AS REQUIRED.
LLS.A N/A EXV.A
LLS.B N/A EXV.B
FAN1 FAN2
FAN3 FAN4
CLR.P (TB5 10,12) CND.P N/A
RMT.A (TB5 11,12)
CC.A1 CC.A2
CC.A3 CC.A4
UL.A1 UL.A2
HGBP
CC.B1 CC.B2
CC.B3 CC.B4
UL.B1 UL.B2