39
Table 18A — Example of Configuring Dual Chiller Control
(Master Chiller)
Table 18B — Example of Configuring Dual Chiller Control
(Slave Chiller)
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
RSET
CRST 0 COOLING RESET TYPE
LLDY 5 LAG START DELAY
5
Scrolling stops
5
Value flashes
10
Select 10
10
Change accepted
LLDY 10
LLBD 168 LEAD/LAG BALANCE DELTA
No change needed. Default set for weekly changeover
LLBL DSBL LEAD/LAG BALANCE SELECT
DSBL
Scrolling stops
DSBL
Value flashes
ENBL
Select Enable
ENBL
Change accepted
LLBL ENBL
SLVA 0 SLAVE ADDRESS
0
Scrolling stops
0
Value flashes
6
Select 6
6
Change accepted
SLVA 6
MSSL MAST MASTER/SLAVE SELECT
No change needed. Default set for Master
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
RSET
CRST 0 COOLING RESET TYPE
LLDY 5 LAG START DELAY
LLBD 168 LEAD/LAG BALANCE DELTA
No change needed. Default set for weekly changeover
LLBL DSBL LEAD/LAG BALANCE SELECT
SLVA 0 SLAVE ADDRESS
MSSL MAST MASTER/SLAVE SELECT
Default set for Master
MAST
Scrolling stops
MAST
Value flashes
SLVE
Select SLVE
SLVE
Change accepted
MSSL
Item/Value/Units scrolls again
LLEN DSBL LEAD/LAG CHILLER ENABLE
DSBL
Scrolling stops
DSBL
Value flashes
ENBL
Select enable
LLEN ENBL
Change accepted
LLEN ENBL LEAD/LAG CHILLER ENABLE
Item/Value/Units scrolls again
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE