Cooling Set Point (4 to 20 mA)
A field supplied
and generated, externally powered 4 to 20 mA signal can be
used to provide the leaving fluid temperature set point. Connect
the signal to TB6-3,5 (+,). See Table 27 for instructions to
enable the function. Figure 22 shows how the 4 to 20 mA sig-
nal is linearly calculated on an overall 10 F to 80 F range for
fluid types (Configuration mode, sub-mode OPT1, item
FLUD) 1 or 2.
Table 27 Menu Configuration of 4 to 20 mA Cooling Set Point Control
MODE
(RED LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
DISP
UNIT
OPT1
OPT2
RSET
SLCT CLSP 0 COOLING SETPOINT SELECT
0 Scrolling Stops
0 Flashing 0
4Select 4
4 Change Accepted
ENTER
ENTER
ENTER
ENTER
ENTER
Fig. 22 Cooling Set Point (4 to 20 mA)
EMM
Energy Management Module
100
(38)
80
(27)
60
(15)
40
(4.4)
20
(-7)
0
(-17)
4 6.3 8.6 10.9 13.1 15.4 17.7 20
4 TO 20 mA SIGNAL TO EMM
SET POINT, F (C)