CL-5
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
C. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
OPTIONS2 (Options Configuration)
PRESS ESCAPE KEY TO DISPLAY ‘OPT2’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
RESETCON (Temperature Reset and Demand Limit)
ITEM DESCRIPTION STATUS UNITS VALUE
CTRL
Control Method 0 = Switch
1 = 7 day sched.
2 = Occupancy
3 = CCN
CCNA
CCN Address 1 to 239
CCNB
CCN Bus Number 0 to 239
BAUD
CCN Baud Rate 1 = 240
2 = 480
3 = 9600
4 = 19,200
5 = 38,400
LOAD
Loading Sequence Select 1 = Equal loading
2 = Staged loading
LLCS
Lead/Lag Circuit Select 1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
LCWT
High LCW Alert Limit 2 to 60 ^F
DELY
Minutes off time 0 to 15 min.
ICE.M
Ice Mode Enable Enable/Disable
ITEM DESCRIPTION STATUS UNITS VALUE
COOLING RESET
CRST
Cooling Reset Type 0 = No Reset
1 = 4-20 mA input
2 = External temp-OAT
3 = Return fluid
4 = External temp-SPT
CRT1
No Cool Reset Temp 0 to 125 °F
CRT2
Full Cool Reset Temp 0 to 125 °F
DGRC
Degrees Cool Reset –30 to 30 ^F
HRST
Heating Reset Type 0 = No Reset
1 = 4-20 mA input
2 = External temp-OAT
3 = Return fluid
4 = External temp-SPT
HRT1
No Heat Reset Temp Not Supported °F
HRT2
Full Heat Reset Temp Not Supported °F
DGRH
Degrees Heat Reset –30 to 30 ^F
DEMAND LIMIT
DMDC
Demand Limit Select 0 = None
1 = External switch input
2 = 4-20 ma input
3 = Loadshed
0
DM20
Demand Limit at 20mA 0 to 100 %
SHNM
Loadshed Group Number 0 to 99
SHDL
Loadshed Demand Delta 0 to 60 %
SHTM
Maximum Loadshed Time 0 to 120 min
DLS1
Demand Limit Switch 1 0 to 100 %
DLS2
Demand Limit Switch 2 0 to 100 %
LEAD/LAG
LLEN
Lead/Lag Chiller Enable Enable/Disable
MSSL
Master/Slave Select Slave/Master
SLVA
Slave Address 0 to 239
LLBL
Lead/Lag Balance Select Enable/Disable
LLBD
Lead/Lag Balance Delta 40 to 400 hours
LLDY
Lag Start Delay 0 to 30 min