Table 21 Setting an Occupied Time Schedule
Table 22 Operating Mode and Sub-Mode Directory
LEGEND
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
SCHD
MON.O 00.00 MONDAY OCCUPIED TIME TIME IN MILITARY FORMAT (HH.MM)
00.00 Scrolling stops
00.00 Hours flash
07.00 Select 7 AM
07.00 Change accepted, minutes flash
07.30 Select 30
07.30 Change accepted
MON.O 07.30 MONDAY OCCUPIED TIME Item/Value/Units scrolls again
SUB-MODE KEYPAD ENTRY ITEM RANGE ITEM EXPANSION COMMENT
MODE
MD01 OFF-ON FSM CONTROLLING CHILLER
MD02 OFF-ON WSM CONTROLLING CHILLER
MD03 OFF-ON MASTER/SLAVE CONTROL
MD04 OFF-ON LOW SOURCE PROTECTION Not Supported
MD05 OFF-ON RAMP LOAD LIMITED
MD06 OFF-ON TIMED OVERRIDE IN EFFECT
MD07 OFF-ON LOW COOLER SUCTION TEMPA
MD08 OFF-ON LOW COOLER SUCTION TEMPB
MD09 OFF-ON SLOW CHANGE OVERRIDE
MD10 OFF-ON MINIMUM OFF TIME ACTIVE
MD11 OFF-ON LOW SUCTION SUPERHEAT A
MD12 OFF-ON LOW SUCTION SUPERHEAT B
MD13 OFF-ON DUAL SETPOINT
MD14 OFF-ON TEMPERATURE RESET
MD15 OFF-ON DEMAND LIMIT IN EFFECT
MD16 OFF-ON COOLER FREEZE PROTECTION
MD17 OFF-ON LO TMP COOL/HI TMP HEAT
MD18 OFF-ON HI TMP COOL/LO TMP HEAT
MD19 OFF-ON MAKING ICE
MD20 OFF-ON STORING ICE
MD21 OFF-ON HIGH SCT CIRCUIT A
MD22 OFF-ON HIGH SCT CIRCUIT B
FSM Flotronic System Manager
SCT Saturated Condensing Temperature
WSM Water System Manager
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER