Table 3 — Status Switches
LEGEND *The OPS can also be added as an accessory.
†The CPCS can be added as an accessory.
Table 4 — Output Relay
LEGEND
OFM —
Outdoor-Fan Motor
*And associated modular units.
†Field-installed accessory unloader.
LEGEND FOR FIG. 1-4
STATUS SWITCH
PIN
CONNECTION
POINT
040-060 (50 Hz)
040-070 (60 Hz)
070
(50 Hz)
080, 230B
090-110,
245B-315B
130
(60 Hz)
130 (50 Hz)
150, 230A-
255A
170,190,
270A,290A,
330A/B,
360A/B, 390B
210, 315A,
390A,
420A/B
Oil Pressure, Ckt B
J7-1, 2 (MBB) Not Used* OPSB OPSB OPSB OPSB OPSB OPSB
Oil Pressure, Ckt A
J7-3, 4 (MBB) Not Used* OPSA OPSA OPSA OPSA OPSA OPSA
Remote On/Off
TB5-13, 14 Field-Installed Relay Closure
Compressor Fault
Signal, B3
J5-8, 12 (CXB) Not Used Not Used Not Used Not Used Not Used CR-B3 CR-B3
Compressor Fault
Signal, B2
J9-2, 12 (MBB) Not Used Not Used CPCS-B2 CR-B2 CR-B2 CR-B2 CR-B2
Compressor Fault
Signal, B1
J9-8, 12 (MBB) CR/CPCS-B1† CPCS-B1 CPCS-B1 CR-B1 CR-B1 CR-B1 CR-B1
Compressor Fault
Signal, A4
J5-5, 12 (CXB) Not Used Not Used Not Used Not Used Not Used Not Used CR-A4
Compressor Fault
Signal, A3
J5-11, 12 (CXB) Not Used Not Used Not Used Not Used CR-A3 CR-A3 CR-A3
Compressor Fault
Signal, A2
J9-5, 12 (MBB) Not Used CPCS-A2 CPCS-A2 CR-A2 CR-A2 CR-A2 CR-A2
Compressor Fault
Signal, A1
J9-11, 12 (MBB) CR/CPCS-A1† CPCS-A1 CPCS-A1 CR-A1 CR-A1 CR-A1 CR-A1
CPCS
Compressor Protection Control System
CR
Control Relay
CXB
Compressor Expansion Board
MBB
Main Base Board
OPS
Oil Pressure Switch, Circuit A or B
RELAY
NO.
DESCRIPTION
K1(MBB)
Energize Compressor A1 and OFM1 (040-110*)
Energize Liquid Line Solenoid Valve for Ckt A (if used)
(040-110*)
Energize Compressor A1, OFM5, and OFM7 (130-210*)
K2 (MBB)
Energize Compressor B1 and OFM2 (040-110*)
Energize Liquid Line Solenoid Valve for Ckt B (if used)
(040-110*)
Energize Compressor B1, OFM6, and OFM8 (130-210*)
K3 (MBB)
Energize Unloader A1 (040-170*)
No Action (190-210*)
K4 (MBB)
Energize Unloader B1 (040-070†, 080-170*)
No Action (190,210*)
K5 (MBB)
No Action (040-060, 50 Hz; 040-070, 60 Hz)
Energize Compressor A2 (070, 50 Hz; 080-210*)
K6 (MBB)
No Action (040-080*)
Energize Compressor B2 (090-210*)
K7 (MBB)
Alarm
K8 (MBB)
Cooler Pump
K9 (MBB)
Energize First Stage of Condenser Fans:
040-050 —OFM3
060-110* — OFM3, OFM4
130 (60 Hz) — OFM1,OFM2
Energize First Stage of Ckt A Condenser Fans:
130 (50 Hz), 150,170* — OFM1
190,210* —OFM1,OFM11
K10 (MBB)
Energize Second Stage of Condenser Fans:
040-050 — OFM4
060-090* — OFM5, OFM6
100,110* — OFM5,OFM6,OFM7,OFM8
130 (60 Hz) — OFM3,OFM4,OFM9,OFM10
Energize First Stage of Ckt B Condenser Fans:
130 (50 Hz), 150,170* — OFM2
190,210* — OFM2,OFM12
K11 (MBB)
Hot Gas Bypass
K1 (CXB)
No Action (040-110*; 130, 60 Hz)
Energize Compressor A3 (130, 50 Hz; 150-210*)
K2 (CXB)
No Action (040-150*)
Energize Compressor B3 (170-210*)
K3 (CXB)
Energize Compressor A4 (210*)
Energize Accessory Unloader A2 (080-110*)
K4 (CXB)
Energize Accessory Unloader B2 (080-110*)
K5 (CXB)
Energize Second Stage of Ckt A Condenser Fans:
130 (50 Hz), 150-210* — OFM3,OFM9
K6 (CXB)
Energize Second Stage of Ckt B Condenser Fans:
130 (50 Hz), 150-210* — OFM4,OFM10
C—
Compressor Contactor
CB
Circuit Breaker
CCN
Carrier Comfort Network
CGF
Compressor Ground Fault
CHT
Cooler Heater Thermostat
CKT
Circuit
CLHR
Cooler Heater Relay
CPCS
Compressor Protection and Control System
CWFS
Chilled Water Flow Switch
CWPI
Chilled Water Pump Interlock
CR
Control Relay
CXB
Compressor Expansion Board
EQUIP GND
Equipment Ground
FB
Fuse Block
FC
Fan Contactor
FCB
Fan Circuit Breaker
FIOP
Factory-Installed Option Package
EMM
Energy Management Module
EXV
Electronic Expansion Valve
FCB
Fan Circuit Breaker
HPS
High-Pressure Switch
LCS
Loss-of-Charge Switch
LEN
Local Equipment Network
MBB
Main Base Board
NEC
National Electrical Code
OAT
Outdoor-Air Temperature
OPS
Oil Pressure Switch
PL
Plug
PW
Part Wind
SN
Sensor (Toroid)
SPT
Space Temperature
TRAN
Transformer
SW
Switch
TB
Terminal Block
TDR
Time Delay Relay
TXV
Thermostatic Expansion Valve
UL
Unloader
XL
Across-the-Line