16
Power Quality Analyzer Model 3945-B
Function Range Display Resolution Accuracy
ApparentEnergy(Vah) 0VAh to 9999MVAh 4 digits ±1% ± 1ct
Unbalance(Vunb,Aunb)
three phase supply
0% to 100%
0.1% ±1% ± 1ct
Phaseangle(V/I;I/I;V/V)
-179°to+180°
1° ±2°
Harmonics ratios
F=40to69Hz
(Vrms>50V)
(rms>Inom/100)
0% to 999%
1 to 50th harmonic
0.1% ±1%+5cts
Harmonics angles
F=40to69Hz
(Vrms>50V)
(rms>Imax/100)
-179°to+180°
1 to 25
26 to 50
1°
±3°
±10°
Total harmonics distortion
(Vthd,Athd,Uthd)
0% to 999%
50
th
harmonic
0.1% ±1%+5cts
CurrentKfactor(Akf) 1 to 99.99
0.01 ±5% ± 1ct
Voltageicker(Vk) 0.00 to 9.99
0.01 notspecied
Vdem, Adem and Udem = Values measured on half cycle (allow to get a measurement with positive and
negative values)
Vpm, Upm and Apm = Peak values min.
3.2.4 Nominal Range of Use
Frequency: 40 to 69Hz
Harmonics:THD(I):0to40%;THD(U):0to20%
Magnetic eld:<40.0A/m(Earth’smagneticeld)
Electrical eld: <3V/m
Relative Humidity: 10 to 90% without condensation
3.2.5 Power Supply
AC Power (internalpowersupply)
Operating Range: 230VAC ± 20% and 110VAC±20%(88to276VAC)
Max Power: 30VA
Battery Power
(allowsuseintheeventofaninterruption)
Type: NiMH 3800 mAh
Output:4-wire(2fortemperatureprobe)
Rated Voltage: 9.6V
Charge Time: 3hrs30minapprox
Battery Life: >8hrswithdisplayon
≥35hrswithdisplayoff(recordingmode)
Operating Temperature:32°to122°F(0°to50°C)
Recharging Temperature: 50°to104°F(10°to40°C)
Storage Temperature: -4to+122°F(-20to+50°C)for≤30days
NOTE: The battery starts to charge when the power cord is connected. When the
battery is charged, the instrument uses the current supplied by the power supply,
without drawing from the battery.