Power Quality Analyzer Model 3945-B
21
Factors affecting accuracy (% of the output signal)
Conditions Range Error
Ambient temperature 14°to131°F(-10°to55°C)
200 ppm/K or
0.2% per 10K
Relative humidity 10° to 35°C 85% < 0.2%
Frequency response 40Hz to 3kHz
40Hzto1kHz:<0.7%
1to3kHz:<2%
Positions of the cable in the jaws
<0.5% to 50/60Hz
Adjacent conductor carrying a
60Hz AC current
Conductor in contact with
the sensor
15mA/A
3.9 AC Current Probe AmpFlex
®
Probe
(3945-B accuracy included)
NOTE: When installing probes, face the arrow on the probe in the direction of
the load.
Nominal Range: 3000AAC
Measurement Range: 10A to 6500AACmax
NOTE: Currents below 9A will be displayed as zero with this probe.
Probe Output Signal: 140mVAC/3000AAC at 50Hz
NOTE: Output is proportional to the amplitude and frequency of the measured current.
Sensor: Length=24"(610mm);Ø=7.64"(190mm)
Length=36"(910mm);Ø=11.46"(290mm)
Safety: EN 61010-1 and 2, Pollution Degree 2, 600V Cat. IV, 1000V Cat. III,
Reference Conditions:
Ambient temperature 64to82°F(18to28°C)
Humidity 20 to 75% of RH
Position of conductor in the sensor
Centered
Continuousmagneticeld <40A/m(earth’smagneticeld)
Externalalternativemagneticeld None present
Externalelectriceld None present
Frequency 10 to 100Hz
Type of signal measured
Sinusoidal