Power Quality Analyzer Model 3945-B
6.6.6 Transients Configuration
The Transients window allows you to set up the criteria for capturing transients.
Figure 6-13
1. Type a name for the session, up to seven characters.
2. Select the date and time to end the search for transients.
3. Select the percent deviation for voltage and current transients. The choices
available from the drop down window are 1, 2, 5, 10, 20, 50 and 100% of the
fullscalerangeofmeasurement.See§5.4fordetailedinformationonthese
values.
4. Selectthemaximumnumberoftransientstocapture(from1to50).
Clear Screen: Clears the eldsthat were already entered for a new transient
search. This button doesn’t cause any changes on the PowerPad
®
.
Write Changes and Start New Transient Search: Initiates searching from new
transients when the OK or Apply button is pressed.
View Transients: Views the stored transients. Download and delete transients
options are also available.
NOTE: The PowerPad
®
loses its scheduled memory if it is powered off before the
recording begins. If it is powered off during the recording, a partial recording will
usually still exist but with the first letter of its name changed to “@”.