10-8 Communicating with Devices on a DH-485 Link
Connections Using Belden 9842 Cable
The table and schematic diagram below shows wire/terminal connections for
Belden 9842 cable.
For this Wire/Pair Connect this Wire To this Terminal
white/orange orange with white stripe 5 - (Data A)
white with orange stripe 4 - (Data B)
blue/white white with blue stripe
cut back - no connection
(1)
(1)
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.
blue with white stripe 3 - (Common)
shield/drain non-jacketed 2 - Shield
Termination
Data A
Data B
Common
Shield
Chassis Ground
WH/OR
OR/WH
6
5
4
3
2
1
WH/BU
BU/WH